Message-ID: <24031142.1075845361094.JavaMail.evans@thyme> Date: Wed, 23 May 2001 14:27:23 -0700 (PDT) From: charles.weldon@enron.com To: mike.coleman@enron.com Subject: RE: Fort Pierce--Maximum Gas Consumtion for Planning Purposes Mime-Version: 1.0 Content-Type: text/plain; charset=us-ascii Content-Transfer-Encoding: 7bit X-From: Weldon, V. Charles X-To: Coleman, Mike X-cc: X-bcc: X-Folder: \Weldon, V. Charles\Weldon, V. Charles\Sent Items X-Origin: WELDON-V X-FileName: Weldon, V. Charles.pst Thanks Mike. Would you mind providing the MW and heat rate assumptions that correspond to these flows just for information purposes. Thanks, Charlie -----Original Message----- From: Coleman, Mike Sent: Wednesday, May 23, 2001 4:10 PM To: Weldon, V. Charles Cc: Breese, Mark; Concannon, Ruth; Gimble, Mathew; Stovall, Darrell; Keenan, Jeffrey; Ottens, Douglas; Bagwell, Jennifer Subject: Fort Pierce--Maximum Gas Consumtion for Planning Purposes Charlie, The new plant max consumption for planning purposes should be set at 2,490 mmBtu/hr HHV. In addition to this it is estimated that the existing Frame 5 may require 335 mmBtur/hr HHV, or a total of 2,825 mmBtu/hr HHV. The plant consumption is based on the maximum combustion turbine requirement, plus a 5% margin, plus duct burning requirement. This should be adequate as a conservative maximum case. Please let me know if you have any questions. Thanks! Mike Coleman